Emergency Lighting Requirements: Exit Sign and Egress Lighting Guide for Contractors

Nov 12, 2026

When the power drops, emergency lights and exit signs are the only thing guiding people out of a building, which is why inspectors look at them closely on every commercial and multifamily job. This guide walks through the emergency lighting requirements contractors and facility managers run into most: where emergency lighting and exit signs go, how much light the code asks for, how long it has to last, how to wire unit equipment, and how to test it once it's in.

A quick note before you start: the requirements below come from the model codes most jurisdictions adopt (the International Building Code, NFPA 101 Life Safety Code and the National Electrical Code). Your local code, any state amendments like California's CBC, and the approved plans always win, so confirm with the plans examiner or fire marshal before you order.

Where emergency lighting is required

In general, emergency lighting has to cover the means of egress, the whole path a person follows from anywhere in the building to the public way. In buildings that need two or more exits, that typically includes:

  • Exit access corridors, aisles and hallways
  • Rooms and spaces that require two or more exits
  • Exit stairways and ramps, including landings
  • Exit passageways and the exit discharge outside the door, out to a safe point
  • Electrical, fire pump and generator rooms, plus some public restrooms, depending on the code edition

Outdoors, the exterior side of exit doors is easy to miss. A wall pack with a built-in emergency battery can light the exit discharge without adding a separate fixture.

How much light: the 1 / 0.1 / 40:1 rule

Both the IBC and NFPA 101 use the same performance numbers, measured along the path of egress at floor level:

  • Initial illumination: an average of at least 1 footcandle, with no point below 0.1 footcandle.
  • At the end of the run time: the levels may drop to an average of 0.6 footcandle and a minimum of 0.06 footcandle.
  • Uniformity: the maximum-to-minimum ratio can't exceed 40 to 1, so you can't hit the average with one bright spot and leave dark gaps.

Spacing is where most jobs come up short. Twin-head units mounted high in a long corridor often leave dark zones between them, so run a photometric layout or check the manufacturer's spacing data instead of guessing.

How long it has to last: 90 minutes

Emergency lighting and exit signs must stay on for at least 90 minutes after normal power fails. That applies whether the backup comes from a battery in each unit, a central inverter or a generator. If you use a generator, it also has to pick up the load within 10 seconds under NEC Article 700.

Exit sign requirements

Exit signs mark every exit and exit access door, and they're required wherever a space needs two or more exits. The main rules in the IBC:

  • Spacing: no point in an exit access corridor can be more than 100 feet from the nearest visible exit sign, or the sign's listed viewing distance if that's shorter.
  • Directional arrows: where the exit isn't immediately visible, add signs with chevrons pointing the way.
  • Letters: at least 6 inches tall with a stroke at least 3/4 inch wide. Internally illuminated, listed LED exit signs meet this.
  • Always lit: signs have to be illuminated at all times and stay lit for 90 minutes on emergency power.
  • Tactile signs: raised-letter and braille "EXIT" signs go next to doors to exit stairways, exit passageways, exit discharge doors and areas of refuge.

Red or green? The model codes don't pick a color, but some cities and states do. A color-selectable universal exit sign lets you set red or green letters in the field, which helps when you're stocking one sign for jobs in different jurisdictions. California also has its own extras, like floor-level exit signs in Group R-1 hotels and motels, so check the CBC on those projects.

Choosing the right equipment

Exit signs and combo units

Stand-alone LED exit signs with a battery are the simplest choice for most doors. Where you need both a sign and egress light at the same spot, an exit/emergency combo saves a box and a fixture. For garages, breezeways and other damp or wet spots, use a wet-location rated unit like the Westgate wet location exit and emergency combo. Low-profile options like the Westgate XIT LED strip combo fit lower ceilings and tight corridors.

Emergency drivers in regular fixtures

In lobbies, offices and corridors where wall-mounted twin heads look out of place, an emergency LED driver turns a normal downlight or troffer into an emergency fixture. Kits like the Nora 20W plug-and-play EM kit include a remote test switch, which makes the monthly test easier.

Self-diagnostic units

Self-testing or self-diagnostic units run their own monthly and annual tests and show a fault light when a battery or lamp fails. They cost more up front, but they cut the labor of hand-testing every unit, which adds up fast in large apartment and commercial buildings.

Wiring unit equipment the right way

Battery units only work if they can sense a real outage. The NEC requires the branch circuit feeding unit equipment to be the same circuit that serves the normal lighting in that area, connected ahead of any local switches. If you wire a unit to a different circuit, a tripped breaker can leave the room dark while the emergency light still sees power. Also make sure the circuit is unswitched, so turning off the lights doesn't drain the batteries.

Testing and maintenance

NFPA 101 requires two tests for battery-powered emergency lighting, with written records kept for the fire marshal:

  • Monthly: a functional test of at least 30 seconds.
  • Annually: a full 90-minute test on battery.

Self-diagnostic units can handle this automatically, but someone still has to check the indicators and log the results.

Get a free layout

Not sure how many units a corridor or stairwell needs? Send us your plans and we'll put together a free lighting layout with fixture counts, spacing and part numbers. You can browse our full emergency and exit lighting collection, including exit signs and emergency lights, and orders over $750 ship free.

FAQ

How long do emergency lights need to stay on?

At least 90 minutes after normal power fails, under both the IBC and NFPA 101.

How many footcandles does emergency lighting need?

An initial average of 1 footcandle with a minimum of 0.1 footcandle along the egress path at floor level. Levels may fall to 0.6 average and 0.06 minimum by the end of the 90 minutes, with a maximum-to-minimum ratio no higher than 40 to 1.

How far apart should exit signs be?

No point in an exit access corridor should be more than 100 feet from the nearest visible exit sign, or the sign's listed viewing distance if it's less.

Do exit signs have to be red or green?

The model codes don't require a color, but some local jurisdictions do. Check with your building department, or use a color-selectable sign.

How often do emergency lights need to be tested?

A 30-second functional test every month and a 90-minute test every year, with records kept. Self-diagnostic units can run these tests automatically.

Can emergency lights be on a separate circuit?

For battery unit equipment, the NEC requires it to be on the same branch circuit as the normal lighting in the area, ahead of local switches, so it switches on when that lighting loses power.