Title 24 Lighting Controls: A Checklist for California Electrical Contractors
Nov 05, 2026If you pull permits in California, Title 24 lighting controls are where plan checks and final inspections most often go sideways. The fixtures can all be high efficacy, but a missing vacancy sensor in a laundry room or a non-dimmable office zone can still earn a correction notice. This checklist walks electrical contractors and facility buyers through the controls Title 24, Part 6 calls for in homes and commercial spaces, and the devices that make each one easy to install.
A quick note before you start: Title 24 is updated every three years, and exceptions depend on space type, size and project scope. Treat this as a field checklist, and confirm the details against the current code cycle and your local building department before you order.
Residential Title 24 lighting controls
Residential lighting rules focus on efficient light sources and making sure lights don't stay on in rooms people pass through.
- High-efficacy everything. Permanently installed luminaires generally need to be high efficacy, which in practice means LED fixtures or lamps certified to Joint Appendix 8 (JA8) in most cases.
- Vacancy sensors in the "pass-through" rooms. Bathrooms, garages, laundry rooms, utility rooms and walk-in closets need at least one luminaire controlled by a vacancy sensor. A vacancy sensor is manual-on, auto-off: the occupant turns the lights on and the sensor turns them off.
- Dimmers or vacancy sensors elsewhere. Most other indoor luminaires need a dimmer or a vacancy sensor. Make sure the LED source is rated for the dimmer you're using.
- Recessed downlights in insulated ceilings. These must be IC rated, airtight and free of screw bases. Our recessed lighting spacing guide covers layout once you've picked the fixture.
- Outdoor lighting. Fixtures mounted to the building need automatic control, typically a photocell plus a motion sensor, or an astronomical time clock.
For bathrooms and laundry rooms, a wall-box sensor is the simplest fix. The Lutron Maestro vacancy-only motion sensor switch runs on 120-277V, works with or without a neutral, and can be set up for single-pole or multi-location control.
Nonresidential Title 24 lighting controls
Commercial requirements stack several layers of control on top of each other. Plan reviewers typically look for each layer on the lighting plans and the compliance forms.
1. Area controls
Each enclosed space needs a manual control that lets occupants turn the lighting on and off, located where they can see the lights it controls.
2. Multi-level lighting
General lighting in most spaces needs to be dimmable or switchable to more than one level, not just full on and off. With LED fixtures, 0-10V dimming is the usual way to meet this. Specify 0-10V drivers on troffers, panels and high bays, and pair them with a compatible dimmer. Browse wall-box and low-voltage options in our dimmers collection.
3. Automatic shutoff
Lighting has to turn off automatically when a space is unoccupied. Offices, conference rooms, classrooms and similar spaces are typically required to use occupancy sensing. In some spaces, such as warehouse aisles, corridors and stairwells, the code calls for partial-off sensors that drop the light level when nobody's there instead of shutting it off completely. Where sensors aren't required, a programmable time switch can handle shutoff.
For a private office, the Lutron Maestro 0-10V motion sensor dimmer combines a 0-10V dimmer and a passive infrared occupancy sensor in one device. Lutron lists up to 900 square feet of major-motion coverage, so one device can cover area control, multi-level dimming and shutoff in a typical small office. Larger or oddly shaped rooms usually need a ceiling sensor. The Lutron LOS2 dual-technology ceiling sensor uses both passive infrared and ultrasonic detection, which helps in rooms where people sit still for long stretches.
4. Daylighting controls
Skylit zones and primary sidelit zones next to windows generally need automatic daylight controls that dim the lighting when enough daylight comes in. Fixture-integrated sensors handle this neatly. The Leviton ZLD1Z-I0W fixture-mount sensor combines PIR occupancy sensing with daylight harvesting and single-zone 0-10V dimming.
5. Demand response
Larger buildings generally need lighting that can be reduced automatically in response to a utility demand response signal. This usually means a networked control system, so plan for it early on big projects.
High bays and warehouses
Warehouses are a common place for partial-off requirements in aisles and open areas. Fixture-mount sensors are often the cleanest way to meet them, since each high bay controls itself. The Leviton OSFLA-I4W high bay occupancy sensor mounts on the fixture, comes with two interchangeable lenses and an aisle mask, and handles 480V circuits without a neutral. If you're also sizing the fixtures, our high bay layout guide walks through the counts.
Alterations and retrofits trigger controls too
Title 24 isn't just for new construction. Replacing or modifying fixtures in an existing building can trigger controls requirements for the altered spaces, depending on how much of the lighting changes. That's why a simple troffer retrofit or parking lot retrofit can end up needing sensors and dimming. Check the alteration rules for your scope before you bid the job, not after the inspector asks.
Paperwork and acceptance testing
Nonresidential lighting controls are documented on the NRCC compliance forms at plan check and the installation forms on site. Many commercial controls also need acceptance testing by a certified Lighting Controls Acceptance Test Technician before final inspection. Residential projects use the CF1R, CF2R and CF3R forms. Build the time for testing and paperwork into your schedule so it doesn't hold up the final.
Contractor checklist
- Every enclosed space has a manual on/off control.
- General lighting is dimmable or multi-level (0-10V drivers plus compatible dimmers).
- Occupancy, vacancy or partial-off sensors are shown where required, with time switches elsewhere.
- Daylight zones near windows and skylights are drawn and controlled separately.
- Outdoor lighting has photocell and motion or time-clock control.
- Residential bathrooms, garages, laundry rooms, utility rooms and walk-in closets have a vacancy sensor.
- Compliance forms and acceptance tests are scheduled.
You'll find every device type above in our lighting controls collection and our occupancy and motion sensors, plus photocells and time switches in timers and photocells. Orders over $750 ship free.
Get a free lighting and controls layout
Controls are much easier to get right on paper. Send us your plans and we'll put together a free lighting layout with fixture counts and suggested sensor and dimming locations, plus part numbers you can order in one go.
FAQ
What is the difference between an occupancy sensor and a vacancy sensor?
An occupancy sensor turns lights on automatically when it detects someone and turns them off after the space is empty. A vacancy sensor requires the occupant to turn the lights on manually, then turns them off automatically. Title 24 calls for vacancy sensors in several residential rooms.
Does Title 24 require dimmable LED lighting?
In most nonresidential spaces, general lighting needs multi-level control, and dimmable LED fixtures with 0-10V drivers are the most common way to meet it. In homes, most luminaires need either a dimmer or a vacancy sensor.
Do LED retrofits have to meet Title 24 controls requirements?
They can. Lighting alterations in existing buildings may trigger controls requirements depending on the scope of work. Check the alteration rules in the current code cycle before bidding.
Which rooms need a vacancy sensor under Title 24 residential rules?
Bathrooms, garages, laundry rooms, utility rooms and walk-in closets need at least one luminaire controlled by a vacancy sensor.
Who does Title 24 lighting controls acceptance testing?
For nonresidential projects, acceptance tests are performed by a certified Lighting Controls Acceptance Test Technician, and the results go on the acceptance forms before final inspection.